Emergency Shutdown Systems for Chlorine Transfer
Safety bulletin or study · August 14, 2002
What happened
This bulletin compares two chlorine releases investigated by the CSB. In both, a railcar unloading hose failed and chlorine was released. In the first incident, an emergency shutdown system malfunctioned, resulting in a release of 48,000 pounds of chlorine and a significant community impact. In the second, the emergency shutdown system worked to minimize the release, and the community was not impacted.
Summary by the US Chemical Safety Board.
Safety recommendations
The CSB made 1 recommendation; none is still open.
To Department of Transportation (DOT)
- 2005-06-I-LA-1Closed - No Longer Applicable
Expand the scope of DOT regulatory coverage to include chlorine railcar unloading operations. Ensure the regulations specifically require remotely operated emergency isolation devices that will quickly isolate a leak in any of the flexible hoses (or piping components) used to unload a chlorine railcar. The shutdown system must be capable of stopping a chlorine release from both the railcar and the facility chlorine receiving equipment. Require the emergency isolation system be periodically maintained and operationally tested to ensure it will function in the event of an unloading system chlorine leak.
More release investigations
- PEMEX Deer Park Chemical Release · Deer Park, TX, 2024
- Cuisine Solutions Ammonia Release · Sterling, VA, 2024
- TS USA Molten Salt Eruption · Chattanooga, TN, 2024
- Honeywell Geismar Chlorine and Hydrogen Fluoride Releases · Geismar, LA, 2023