What happened

This bulletin compares two chlorine releases investigated by the CSB. In both, a railcar unloading hose failed and chlorine was released. In the first incident, an emergency shutdown system malfunctioned, resulting in a release of 48,000 pounds of chlorine and a significant community impact. In the second, the emergency shutdown system worked to minimize the release, and the community was not impacted.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 1 recommendation; none is still open.

To Department of Transportation (DOT)

  • 2005-06-I-LA-1Closed - No Longer Applicable

    Expand the scope of DOT regulatory coverage to include chlorine railcar unloading operations. Ensure the regulations specifically require remotely operated emergency isolation devices that will quickly isolate a leak in any of the flexible hoses (or piping components) used to unload a chlorine railcar. The shutdown system must be capable of stopping a chlorine release from both the railcar and the facility chlorine receiving equipment. Require the emergency isolation system be periodically maintained and operationally tested to ensure it will function in the event of an unloading system chlorine leak.