Aghorn Operating Inc. Waterflood Station Hydrogen Sulfide Release
Odessa, TX · October 26, 2019
What happened
A release of hydrogen sulfide led to the death of one worker as well as a member of the public.
Summary by the US Chemical Safety Board.
Safety recommendations
The CSB made 9 recommendations; none is still open.
To Aghorn Operating Inc.
- 2020-01-I-TX-1Closed - Acceptable Action
For all waterflood stations where the potential exists to expose workers or non-employees to H 2 S concentrations at or above 10 ppm, mandate the use of personal H 2 S detection devices as an integral part of every employee or visitor personal protective equipment (PPE) kit prior to entering the vicinity of the facility. Ensure detector use is in accordance with manufacturer specifications.
- 2020-01-I-TX-2Closed - Acceptable Action
For all Aghorn facilities, develop a site-specific, formalized and comprehensive Lockout / Tagout program, to include policies, procedures, and training, to protect workers from energized equipment hazards, such as exposure to H 2 S. Ensure the program meets the requirements outlined in 29 CFR 1910.147 and includes energy control procedures, training, and periodic inspections.
- 2020-01-I-TX-3Closed - Acceptable Alternative Action
For all waterflood stations where the potential exists to expose workers to H 2 S concentrations at or above 10 ppm, commission an independent and comprehensive analysis of each facility design vis-à-vis ventilation and mitigation systems to ensure that, in the event of an accidental release, workers are protected from exposure to toxic gas levels.
- 2020-01-I-TX-4Closed - Acceptable Action
For all waterflood stations where the potential exists to expose workers or non-employees to H 2 S concentrations at or above 10 ppm, develop and demonstrate the use of a safety management program that includes a focus on protecting workers and non-employees from H 2 S. This program should include risk identification, assessment, mitigation, and monitoring of design, procedures, maintenance and training related to H 2 S. This program must be in compliance with 29 CFR 1910.1000 – Air Contaminants and 29 CFR 1910.147 – The Control of Hazardous Energy (Lockout / Tagout).
- 2020-01-I-TX-5Closed - Acceptable Action
For all waterflood stations where the potential exists to expose workers to H 2 S concentrations at or above 10 ppm, ensure the H 2 S detection and alarm systems are properly maintained and configured, and develop site-specific detection and alarm programs and associated procedures based on manufacturer specifications, current codes, standards, and industry good practice guidance. The program must address installation, calibration, inspection, maintenance, training and routine operations.
- 2020-01-I-TX-6Closed - Acceptable Action
For all waterflood stations where the potential exists to expose workers or non-employees within the perimeter of the facility to H2S concentrations at or above 10 ppm, ensure that the H2S detection and alarm system designs employ multiple layers of alerts unique to H2S, such as with the use of both audible and visual mediums, so that workers and non-employees within the perimeter of the facility would be alerted to a significant release. The system design must meet manufacturer specifications, current codes, standards, and industry good practice guidance.
- 2020-01-I-TX-7Closed - Acceptable Action
For all waterflood stations where the potential exists to expose non-employees to H2S concentrations at or above 10 ppm, develop and implement a formal, written, site-specific security program to prevent unknown and unplanned entrance of those not employed by Aghorn, starting with a requirement for employees to lock access gates upon entering and departing the facility.
To Occupational Safety and Health Administration (OSHA)
- 2020-01-I-TX-8Closed - Acceptable Action
Issue a safety information product (such as a safety bulletin or safety alert) that addresses the requirements for protecting workers from hazardous air contaminants and from hazardous energy.
To Texas Railroad Commission (RRC)
- 2020-01-I-TX-9Closed - Acceptable Action
Develop and send a Notice to Operators to all oil and gas operators that fall under the jurisdiction of the Railroad Commission of Texas that describes the safety issues described in this report, including: 1. Nonuse of Personal H2S Detector 2. Nonperformance of Lockout / Tagout 3. Confinement of H2S Inside Pump House 4. Lack of Safety Management Program 5. Nonfunctioning H2S Detection and Alarm System 6. Deficient Site Security
More release investigations