Combustible Dust Explosion and Fire
CTA Acoustics Dust Explosion and Fire
Corbin, KY · February 20, 2003
What happened
On February 20, 2003, an explosion and fire damaged the CTA Acoustics manufacturing plant in Corbin, Kentucky, fatally injuring seven workers. The facility produced fiberglass insulation for the automotive industry. CSB investigators have found that the explosion was fueled by resin dust accumulated in a production area, likely ignited by flames from a malfunctioning oven. The resin involved was a phenolic binder used in producing fiberglass mats.
Summary by the US Chemical Safety Board.
Safety recommendations
The CSB made 22 recommendations; none is still open.
To American Chemistry Council (ACC)
- 2003-09-I-KY-19Closed - Acceptable Action
Communicate the findings and recommendations of this report to your membership. Emphasize that dusts from phenolic resins can explode
To Borden Chemical, Inc.
- 2003-09-I-KY-11Closed - Acceptable Action
Ensure MSDSs for phenolic resins include, at a minimum, warnings that dust from these products can be explosive.
- 2003-09-I-KY-12Closed - Acceptable Action
Develop and distribute educational material, in addition to MSDSs, to inform customers of the explosion hazard of phenolic resin dust.
- 2003-09-I-KY-13Closed - Acceptable Action
Communicate the findings and recommendations of this report to your customers that purchase phenolic resin.
To CertainTeed Corporation
- 2003-09-I-KY-9Closed - Acceptable Action
Evaluate your facilities that handle combustible dusts and ensure that good practice guidelines such as NFPA 654 are followed.
- 2003-09-I-KY-10Closed - Acceptable Action
Ensure that company design standard's applicable to facilities that handle combustible dust's incorporate good engineering practices to prevent dust explosions, such as NFPA 654.
To CTA Acoustics, Inc.
- 2003-09-I-KY-1Closed - Acceptable Action
Develop a combustible dust safety program using good practice guidelines, such as NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. At a minimum: Minimize surfaces where combustible dust could accumulate in the design or modification of the plant.
- 2003-09-I-KY-2Closed - Acceptable Action
Develop a combustible dust safety program using good practice guidelines, such as NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. At a minimum: Ensure phenolic resin-handling facilities are designed to prevent the spread of fires or explosions involving combustible dust. Options include measures such as the use of firewalls and blast-resistant construction.
- 2003-09-I-KY-3Closed - Acceptable Action
Develop a combustible dust safety program using good practice guidelines, such as NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. At a minimum: Prevent the unsafe accumulation and dispersion of combustible dust by frequently cleaning process areas, including locations above production lines.
- 2003-09-I-KY-4Closed - Acceptable Action
Develop a combustible dust safety program using good practice guidelines, such as NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. At a minimum: Minimize the dispersion of combustible dust by using appropriate dust-cleaning methods and tools.
- 2003-09-I-KY-5Closed - Acceptable Action
Develop a combustible dust safety program using good practice guidelines, such as NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. At a minimum: Address the dangers of combustible dust and the prevention of dust explosions in the hazard communication training program.
- 2003-09-I-KY-6Closed - Acceptable Action
Conduct hazard assessments of ovens to ensure that fire detection and suppression systems are adequate, using good practice guidelines such as NFPA 86, Standard for Ovens and Furnaces.
- 2003-09-I-KY-7Closed - Acceptable Action
Develop procedures to maintain safety during nonroutine operating conditions, such as the loss of oven temperature control.
- 2003-09-I-KY-8Closed - Acceptable Action
Revise the incident investigation program to ensure that the underlying causes of incidents such as fires are identified and corrective actions implemented.
To FM Global
- 2003-09-I-KY-16Closed - Acceptable Action
Incorporate the findings and recommendations of this report in your training of employees who conduct inspections at facilities that may handle combustible dusts.
To International Code Council (ICC)
- 2003-09-I-KY-20Closed - Acceptable Action
Communicate the findings and recommendations of this report to your membership.
To Kentucky Office of Housing, Buildings, and Construction
- 2003-09-I-KY-17Closed - Acceptable Action
Incorporate the findings and recommendations of this report in your continuing training of inspectors, plan reviewers, technical advisors, and fire marshal general inspectors who interface with facilities that may handle combustible dusts.
- 2003-09-I-KY-18Closed - Exceeds Recommended Action
Identify sites that handle combustible dusts when facilities apply for new or modified construction permits, and use this information to help prioritize establishments that will be inspected by the fire marshal.
To Kentucky Office of Occupational Safety and Health
- 2003-09-I-KY-14Closed - Acceptable Action
Develop and distribute an educational bulletin on the prevention of combustible dust explosions.
- 2003-09-I-KY-15Closed - Acceptable Action
Enhance the training program for compliance officers regarding the recognition and prevention of combustible dust explosion hazards.
To National Fire Protection Association (NFPA)
- 2003-09-I-KY-21Closed - Acceptable Action
Communicate the findings and recommendations of this report to your membership.
To Society of the Plastics Industry- Phenolic Division
- 2003-09-I-KY-22Closed - Acceptable Action
Communicate the findings and recommendations of this report to your membership.