Hoeganaes Corporation Fatal Flash Fires

Gallatin, TN · January 31, 2011

What happened

Three combustible dust incidents over a six month period occurred at the Hoeganaes facility in Gallatin, TN, resulting in fatal injuries to five workers. The facility produces powdered iron and is located about twenty miles outside of Nashville.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 13 recommendations; none is still open.

To City of Gallatin, TN

  • 2011-4-I-TN-11Closed - Unacceptable Action/No Response Received

    Require all facilities covered by IFC Chapter 13 (2006 edition) to conform to NFPA standards for combustible dusts including NFPA 484.

To City of Gallatin, TN Fire Department

  • 2011-4-I-TN-12Closed - Acceptable Action

    Ensure that all industrial facilities in the City of Gallatin are inspected periodically against the International Fire Code. All facility inspections shall be documented.

  • 2011-4-I-TN-13Closed - Acceptable Action

    Implement a program to ensure that fire inspectors and response personnel are trained to recognize and address combustible dust hazards.

To Hoeganaes Corporation

  • 2011-4-I-TN-6Closed - Unacceptable Action/No Response Received

    Conduct periodic independent audits of the Hoeganaes Gallatin facility for compliance with the following NFPA standards, using knowledgeable experts, and implement all recommended corrective actions: NFPA 484, Standard for Combustible Metals, Metal Powders, and Metal Dusts NFPA 499, Recommended Practice for the Classification of Combustible Dusts and of Hazardous Locations for Electrical Installations in Chemical Process Areas NFPA 497, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas NFPA 2, Hydrogen Technologies Code NFPA 2113, Standard on Selection, Care, Use, and Maintenance of Flame-Resistant Garments for Protection of Industrial Personnel Against Flash Fire

  • 2011-4-I-TN-7Closed - Unacceptable Action/No Response Received

    Develop training materials that address combustible dust and plant-specific metal dust hazards and train all employees and contractors. Require periodic (e.g., annual) refresher training for all employees and contractors.

  • 2011-4-I-TN-8Closed - Unacceptable Action/No Response Received

    Implement a preventive maintenance program and leak detection and leak mitigation procedures for all flammable gas piping and gas processing equipment.

  • 2011-4-I-TN-9Closed - Unacceptable Action/No Response Received

    Develop and implement a near-miss reporting and investigation policy that includes the following at a minimum: Ensure facility-wide worker participation in reporting all near-miss events and operational disruptions (such as significant iron powder accumulations, smoldering fires, or unsafe conditions or practices) that could result in worker injury. Ensure that the near-miss reporting program requires prompt investigations, as appropriate, and that results are promptly circulated throughout the Hoeganaes Corporation. Establish roles and responsibilities for the management, execution, and resolution of all recommendations from near-miss investigations Ensure the near-miss program is operational at all times (e.g. nights, weekends, holiday shifts).

To International Code Council (ICC)

  • 2011-4-I-TN-4Closed - Acceptable Action

    Revise IFC Chapter 22 Combustible Dust Producing Operations; Section 2204.1 Standards, to require mandatory compliance and enforcement with the detailed requirements of the NFPA standards cited in the chapter, including NFPA 484.

To Metal Powders Producers Association (MPPA)

  • 2011-4-I-TN-10Closed - Acceptable Action

    Communicate the findings of this report to all your members, e.g. through a safety article in an upcoming monthly newsletter.

To Occupational Safety and Health Administration (OSHA)

  • 2011-4-I-TN-1Closed - Reconsidered/Superseded

    (Superseded by 2017-07-I-WI-R10 from the Didion Milling Co. investigation) Ensure that the forthcoming OSHA Combustible Dust Standard includes coverage for combustible metal dusts including iron and steel powders.

  • 2011-4-I-TN-2Closed - Reconsidered/Superseded

    (Superseded by 2017-07-I-WI-R10 from the Didion Milling Co. investigation) Develop and publish a proposed combustible dust standard for general industry within one year of the approval of this case study.

  • 2011-4-I-TN-3Closed - Acceptable Alternative Action

    Revise the Combustible Dust National Emphasis Program (NEP) to add industry codes for facilities that generate metal dusts (e.g., North American Industrial Classification System, NAICS, code 331111 Iron and Steel Mills, and other applicable codes not currently listed). Send notification letters to all facilities nationwide under these codes to inform them of the hazards of combustible metal dusts and NEP coverage.

To Tennessee Division of Occupational Safety & Health (TOSHA)

  • 2011-4-I-TN-5Closed - Acceptable Action

    Revise the state-adopted Dust National Emphasis Program (NEP) to add industry codes for facilities that generate metal dusts (e.g., North American Industrial Classification System, NAICS, code 331111 Iron and Steel Mills, and other applicable codes not currently listed). Send notification letters to all facilities statewide under these codes to inform them of the hazards of combustible metal dusts and NEP coverage.