Skip to main content

Combustible Dust Explosion and Fire

US Ink Fire

East Rutherford, NJ · October 9, 2012

What happened

An explosion and fire injured 7 workers at the US Ink facility.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 8 recommendations; none is still open.

To New Jersey Department of Community Affairs

  • 2013-01-I-NJ-3Closed - Acceptable Action

    Revise the exemption for “manufacturing, production, and process equipment” under the New Jersey Uniform Construction Code (N.J.A.C 5:23-2.2) to require that equipment involved in processing, handling, or conveying combustible dust comply with the design and operating requirements of the current edition of the International Building Code.

  • 2013-01-I-NJ-4Closed - Acceptable Action

    Develop and implement training for local code officials on the National Fire Protection Association (NFPA) standards referenced in the New Jersey adoption of the International Building Code (IBC) for occupancies with a high hazard classification (Group H); specifically, include training on equipment that handles combustible dust and the hazards involved.

  • 2013-01-I-NJ-5Closed - No Longer Applicable

    Promulgate a regulation that requires all occupancies handling hazardous materials to inform the local enforcement agency of any type of construction or installation of equipment at an industrial or manufacturing facility. Also require local enforcement agencies to evaluate the information to determine whether a construction permit is required.

To Occupational Safety and Health Administration (OSHA)

  • 2013-01-I-NJ-1Closed - Acceptable Action

    Add North American Industry Classification System (NAICS) Code 325910, Printing Ink Manufacturing, to the list of industries in Appendix D-1 or Appendix D-2 of Combustible Dust National Emphasis Program (NEP), Directive CPL 03-00-008.

  • 2013-01-I-NJ-2Closed - Reconsidered/Superseded

    Communicate with all OSHA Area Offices to encourage appropriate application of the following existing provisions of the Combustible Dust NEP, Directive CPL 03-00-008: Paragraph IX, Section A2, indicates that area offices may add to their Combustible Dust NEP establishment lists those facilities in their jurisdictions with a Standard Industrial Classification System code, NAICS code, or both (other than those listed in Appendices D-1 and D-2 of the Combustible Dust NEP directive) if those facilities have a known pattern of combustible dust hazards. Paragraph IX, Section B4, indicates that if a fatality or catastrophe investigation is performed at a facility because of a combustible dust deflagration or explosion, the inspector shall use the guidelines in Fatality/Catastrophe Investigation Procedures, Directive CPL 02-00-137, and in the Combustible Dust NEP, Directive CPL 03-00-008.

To US Ink/Sun Chemical Corporation

  • 2013-01-I-NJ-6Closed - Acceptable Action

    At the US Ink East Rutherford facility, install automatic fire alarm systems consistent with NFPA 72 (the National Fire Alarm Code) in manufacturing areas (such as mixing) where heat generation could occur.

  • 2013-01-I-NJ-7Closed - Acceptable Action

    Revise the Capital Appropriations/Asset Request (CAR) form procedure for new installations and modifications to existing equipment to require at a minimum the following: Process hazard analysis (PHA) Management of change (MOC) Review of engineering drawings for permits Safety management of contractors Training of plant operators based on applicable dust collection system guidelines and standards, including NFPA 91 and NFPA 654.

  • 2013-01-I-NJ-8Closed - Acceptable Action

    Develop and implement a management of organizational change protocol to allow for the transfer of knowledge and information to new personnel, at a minimum including initial or refresher training in the following: Safety and health procedures Lessons learned from previous incidents Technical information for equipment Routine plant operations.