Louisville, KY · March 21, 2011

What happened

Two workers were killed and two others injured as a result of a fire and explosion that occurred at the Carbide Industries facility located in Louisville, KY; the facility produces calcium carbide products.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 3 recommendations; none is still open.

To Carbide Industries

  • 2011-5-I-KY-2Closed - No Longer Applicable

    Modify the design and procedures for the electric arc furnace and re lated structures including the control room to comply with the NFPA standard developed per R1 of this case study.

  • 2011-5-I-KY-3Closed - Acceptable Action

    Implement a mechanical integrity program for the electric arc furnace and cover, including preventive maintenance based on periodic inspections, and timely replacement of the furnace cover. At a minimum, the program should include factors such as leak detection and repair and refractory lining wear.

To National Fire Protection Association (NFPA)

  • 2011-5-I-KY-1Closed - Reconsidered/Superseded

    Establish a committee to evaluate and develop a standard that defines the safety requirements for electric arc furnaces operated with flammable materials and low oxygen atmospheres. At a minimum, establish requirements that electric arc furnaces containing flammables have: • Adequate safety instrumentation and controls to prevent explosions and overpressure events; • Mechanical integrity and inspection programs; • A documented siting analysis to ensure that control rooms and other occupied areas are adequately protected.