Chemical Manufacturing - Fire and Explosion

Shell Polymers Furnace Explosion and Fire

Monaca, PA · June 4, 2025

What happened

On June 4, 2025, at approximately 2:19 p.m. local time, the Shell Polymers Monaca facility experienced an explosion in an ethane cracking furnace. The incident resulted in a fire, a release of ethylene cracked gas and combustion products, and estimated property damage of $95 million.

Summary by the US Chemical Safety Board.

Lessons

Hominin's reading of what the investigation asks others to change. Each lesson names the recommendations it comes from.

  1. Severe scenarios need more than procedures

    The plant was asked to find deviations in its ethane cracking unit hazard analysis that are handled only by administrative controls, and to add inherently safer design or engineered controls wherever one could cause a death, serious injury or major damage.

    From recommendation 2025-05-I-PA-1

  2. Stop cracked gas flowing back into a furnace

    The plant was asked to install and maintain an engineered control that prevents cracked gas from flowing back into a furnace in every mode of furnace operation.

    From recommendation 2025-05-I-PA-2

Safety recommendations

The CSB made 2 recommendations; 2 are still open.

To Shell Polymers Monaca

  • 2025-05-I-PA-1Open - Awaiting Response or Evaluation/Approval of Response

    Review the Shell Polymers Monaca Ethane Cracking Unit process hazard analysis to identify process deviations that are addressed solely with administrative controls. Implement an inherently safer design or an engineered control for any scenario identified that could result in a fatality, serious injury, or substantial property damage.

  • 2025-05-I-PA-2Open - Awaiting Response or Evaluation/Approval of Response

    Based on licensor input and good industry practices, such as ANSI/ISA-61511-2-2018 / IEC 61511-2:2016, Functional Safety – Safety Instrumented Systems for the Process Industry Sector – Part 2: Guidelines for the application of IEC 61511-1:2016 and Part 3: Guidance for the Determination of the Required Safety Integrity Levels, implement and maintain an engineered control to prevent backflow of cracked gas into a furnace during all modes of furnace operation.

More chemical manufacturing - fire and explosion investigations