Chemical Manufacturing - Fire and Explosion

AirGas Facility Fatal Explosion

Pensacola, FL · August 28, 2016

What happened

The CSB's final report was released at a news conference in Pensacola, FL on 4/20/2017.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 6 recommendations; none is still open.

To ACD, LLC

  • 2016-04-I-FL-5Closed - Acceptable Action

    Provide effective warning about nitrous oxide decomposition hazards Modify nitrous oxide pump product literature to include warnings about nitrous oxide decomposition hazards, illustrated by examples from historical incidents, and refer users to this CSB investigation report for additional information.

To AirGas, Inc.

  • 2016-04-I-FL-1Closed - Exceeds Recommended Action

    The goal of 2016-04-I-FL-R1 is to prevent all nitrous oxide explosions at its facilities, while preventing harm to workers and the public. Following the August 28, 2016, incident, the company began a comprehensive initiative to review its nitrous oxide production facilities, trucking fleet, and cylinder-filling operations. The scope of the ongoing Air Liquide initiative is shown in Table 1. Complete the development and implementation of the company’s nitrous oxide business process safety initiative as shown in Table 1, consistent with the findings, conclusions, and recommendations contained in this report.

To Compressed Gas Association (CGA)

  • 2016-04-I-FL-2Closed - Exceeds Recommended Action

    Safety Management System for Nitrous Oxide Manufacturing Develop and implement a safety management system standard for nitrous oxide manufacturing, to manage known process safety hazards, including nitrous oxide decomposition, which includes appropriate elements based on chemical industry good practice guidance, such as CCPS Guidelines for Risk Based Process Safety, Essential Practices for Managing Chemical Reactivity Hazards, and Guidelines for Implementing Process Safety Management.

  • 2016-04-I-FL-3Closed - Acceptable Alternative Action

    Ensure Effective Flame Arrestor Design Modify Compressed Gas Association (CGA) standard CGA G-8.3, Safe Practices for Storage and Handling of Nitrous Oxide to require testing of safety devices, such as strainers used as flame arrestors, for applications where a safety device is used to quench a nitrous oxide decomposition reaction. To ensure that these safety devices meet the intended purpose, the user should test the safety device by simulating conditions of use. In addition, require users to document the required performance standard or test protocol followed.

  • 2016-04-I-FL-4Closed - Acceptable Action

    Require Pump Run-Dry Safety Interlocks Apply ISA-84 Modify Compressed Gas Association (CGA) standard CGA G-8.3, Safe Practices for Storage and Handling of Nitrous Oxide to reference and require applying International Society of Automation (ISA) standard ISA-84, Functional Safety: Safety Instrumented Systems for the Process Industry Sector to safety interlocks such as the nitrous oxide pump “run-dry” shutdown.

To Cryostar USA, LLC

  • 2016-04-I-FL-6Closed - Acceptable Action

    Provide effective warning about nitrous oxide decomposition hazards Modify nitrous oxide pump product literature to include warnings about nitrous oxide decomposition hazards, illustrated by examples from historical incidents, and refer users to this CSB investigation report for additional information.

More chemical manufacturing - fire and explosion investigations