Skip to main content

Explosion and Fire

Acetylene Service Company Gas Explosion

Perth Amboy, NJ · January 25, 2005

What happened

On January 25, 2005, a gas explosion killed three workers at the Acetylene Service Company plant in Perth Amboy, NJ. The blast originated in a wooden shed located near six large storage tanks that received liquid waste from the plant's acetylene generating system.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 5 recommendations; none is still open.

To Acetylene Service Company (ASCO)

  • 2005-3-I-NJ-1Closed - No Longer Applicable

    Improve isolation on acetylene generator water lines by incorporating a double-block-and-bleed with a vent to a safe location, or other isolation means of comparable effectiveness.

  • 2005-3-I-NJ-2Closed - No Longer Applicable

    Implement an effective Process Safety Management program, in accordance with OSHA 1910.119. Include written operating procedures and checklists that are understood by the workers responsible for using them. Train workers on the procedures and periodically confirm that they are being properly followed.

To Occupational Safety and Health Administration (OSHA)

  • 2005-3-I-NJ-5Closed - Acceptable Action

    Update the OSHA 1910.102 Acetylene Standard (a. Cylinders, b. Piped Systems, and c. Generators and filling cylinders) to remove the existing references to unavailable and obsolete Compressed Gas Association Pamphlets (CGA G-1-1966, G 1.3-1959, G 1.4-1966). As an alternative, consider incorporating by reference NFPA 51A Standard for Acetylene Cylinder Charging Plants.

To Rexarc, Inc.

  • 2005-3-I-NJ-3Closed - Acceptable Action

    Immediately inform existing acetylene generator users that the check valve did not prevent acetylene gas backflow in this incident. Recommend interim actions be taken to ensure that Rexarc check valves in service on acetylene production equipment will operate reliably.

  • 2005-3-I-NJ-4Closed - Acceptable Action

    Replace check valves of this or similar design supplied by Rexarc with valves that will perform more reliably in recycle water service.