Skip to main content

Explosion and Fire

Dow Louisiana Operations Explosions

Plaquemine, LA · July 14, 2023

What happened

On July 14, 2023, at approximately 9:15 p.m., multiple explosions occurred in the Dow Louisiana Operations Glycol II Ethylene Oxide Finishing unit in Plaquemine, Louisiana. This incident resulted in substantial property damage at the plant, but no injuries.

Summary by the US Chemical Safety Board.

Lessons

Hominin's reading of what the investigation asks others to change. Each lesson names the recommendations it comes from.

  1. Monitor the inerting you depend on

    The company was asked to find, at all its ethylene oxide facilities, the process lines that should be or are inerted but are not continuously monitored during normal operation.

    From recommendation 2023-03-I-LA-1

  2. A vessel entered for work must be left clean

    Three confined space and tank entry standards were asked to add guidance or requirements ensuring that vessels which have undergone confined space entry are left clean afterwards.

    From recommendations 2023-03-I-LA-4, 2023-03-I-LA-2, 2023-03-I-LA-3

Safety recommendations

The CSB made 4 recommendations; 4 are still open.

To American Society of Safety Professionals (ASSP)

  • 2023-03-I-LA-4Open - Awaiting Response or Evaluation/Approval of Response

    Update ANSI/ASSP Z117.1 Safety Requirements for Entering Confined Spaces to provide guidance on how to ensure that vessels that have undergone confined space entry are left clean and ready for startup after the entries are completed.

To Dow Chemical Company

  • 2023-03-I-LA-1Open - Acceptable Response or Alternate Response

    At all Dow ethylene oxide facilities, identify all process lines in ethylene oxide service that should be or are inerted and currently are not continuously monitored during normal operation. For all lines identified, determine whether the line can be eliminated, and if not, establish proper controls such as inerting and monitoring to ensure the process line is adequately inerted.

To National Fire Protection Association (NFPA)

  • 2023-03-I-LA-2Open - Awaiting Response or Evaluation/Approval of Response

    Update NFPA 350 Guide for Safe Confined Space Entry and Work to provide guidance on how to ensure that vessels that have undergone confined space entry are left clean and ready for startup after the entries are completed.

  • 2023-03-I-LA-3Open - Awaiting Response or Evaluation/Approval of Response

    Update NFPA 326 Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair to provide requirements for to ensure that vessels that have undergone confined space entry are left clean and ready for startup after the entries are completed.