Oil and Refining - Fire and Explosion
Tosco Avon Refinery Petroleum Naphtha Fire
Martinez, CA · February 23, 1999
What happened
On February 23, 1999, a fire occurred in the crude unit at Tosco Corporation. Avon oil refinery in Martinez, California. Workers were attempting to replace piping attached to a 150-foot-tall fractionator tower while the process unit was in operation. During removal of the piping, naphtha was released onto the hot fractionator and ignited. The flames engulfed five workers located at different heights on the tower. Four men were killed, and one sustained serious injuries.
Summary by the US Chemical Safety Board.
Safety recommendations
The CSB made 7 recommendations; none is still open.
To American Petroleum Institute (API)
- 1999-014-I-CA-5Closed - Acceptable Action
Communicate the findings of this report to your membership.
To National Petrochemical and Refiners Association (NPRA)
- 1999-014-I-CA-5Closed - Acceptable Action
Communicate the findings of this report to your membership.
To Paper, Allied-Industrial, Chemical and Energy Workers International Union (PACE)
- 1999-014-I-CA-5Closed - Acceptable Action
Communicate the findings of this report to your membership.
To Tosco Corporation
- 1999-014-I-CA-1Closed - Acceptable Action
Conduct periodic safety audits of your oil refinery facilities in light of the findings of this report. At a minimum, ensure that: Audits assess the following: - Safe conduct of hazardous nonroutine maintenance - Management oversight and accountability for safety - Management of change program - Corrosion control program. Audits are documented in a written report that contains findings and recommendations and is shared with the workforce at the facility. Audit recommendations are tracked and implemented.
To Ultramar Diamond Shammock Golden Eagle Refinery
- 1999-014-I-CA-2Closed - Acceptable Action
Implement a program to ensure the safe conduct of hazardous nonroutine maintenance. At a minimum, require that: A written hazard evaluation is performed by a multidisciplinary team and, where feasible, conducted during the job planning process prior to the day of job execution. Work authorizations for jobs with higher levels of hazards receive higher levels of management review, approval, and oversight. A written decision-making protocol is used to determine when it is necessary to shut down a process unit to safely conduct repairs. Management and safety personnel are present at the job site at a frequency sufficient to ensure the safe conduct of work. Procedures and permits identify the specific hazards present and specify a course of action to be taken if safety requirements such as controlling ignition sources, draining flammables, and verifying isolation are not met. The program is periodically audited, generates written findings and recommendations, and implements corrective actions.
- 1999-014-I-CA-3Closed - Acceptable Action
Ensure that MOC reviews are conducted for changes in operating conditions, such as altering feedstock composition, increasing process unit throughput, or prolonged diversion of process flow through manual bypass valves.
- 1999-014-I-CA-4Closed - Acceptable Action
Ensure that your corrosion management program effectively controls corrosion rates prior to the loss of containment or plugging of process equipment, which may affect safety.
More oil and refining - fire and explosion investigations
- BP - Husky Oregon Chemical Release and Fire · Oregon, OH, 2022
- Philadelphia Energy Solutions (PES) Refinery Fire and Explosions · Philadelphia, PA, 2019
- Husky Energy Superior Refinery Explosion and Fire · Superior, WI, 2018
- ExxonMobil Baton Rouge Refinery Chemical Release and Fire · Baton Rouge, LA, 2016