Chemical Distribution - Fire and Explosion
Herrig Brothers Farm Propane Tank Explosion
Albert City, IA · April 9, 1998
What happened
On April 9, 1998, an 18,000-gallon propane tank exploded at the Herrig Brothers farm in Albert City, Iowa. The explosion killed two volunteer firefighters and injured seven other emergency response personnel. Several buildings were also damaged by the blast.
Summary by the US Chemical Safety Board.
Safety recommendations
The CSB made 9 recommendations; none is still open.
To Fire Service Institute of Iowa State University
- 1998-007-I-IA-7Closed - Acceptable Action
Ensure that fire fighter training materials address proper response procedures for BLEVEs.
To Herring Brothers Farm
- 1998-007-I-IA-1Closed - Acceptable Action
Install protection (i.e., fencing or barricades) to protect aboveground propane pipes from possible damage from vehicles.
- 1998-007-I-IA-2Closed - Acceptable Action
Install properly sized propane outlet piping from excess flow valves.
To Iowa State Fire Marshal
- 1998-007-I-IA-3Closed - Acceptable Action
Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum the following element: Designation by regulation of the party (such as a facility owner or installer) who is responsible for submitting planned construction or modification documents to the State Fire Marshall.
- 1998-007-I-IA-4Closed - Acceptable Action
Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: · Procedures for approving the plans for new or modified installations
- 1998-007-I-IA-5Closed - Acceptable Action
Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: Procedures governing the issuance and posting of permits authorizing the use of equipment
- 1998-007-I-IA-6Closed - Unacceptable Action/No Response Received
Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: · On-site inspections of new, modified, and existing propane and other Liquefied Petroleum Gas storage facilities that are covered by Iowa state law.
To National Propane Gas Association (NPGA)
- 1998-007-I-IA-8Closed - Acceptable Action
Ensure that fire fighter-training materials address proper response procedures for BLEVEs.
- 1998-007-I-IA-9Closed - Acceptable Action
Distribute the CSB findings and recommendations in this report to NPGA members.
More chemical distribution - fire and explosion investigations
- Enterprise Pascagoula Gas Plant Explosion and Fire · Moss Point, MS, 2016
- West Fertilizer Explosion and Fire · West, TX, 2013
- Caribbean Petroleum Corporation (CAPECO) Refinery Tank Explosion and Fire · Bayamón, PR, 2009
- Barton Solvents Flammable Liquid Explosion and Fire · Des Moines, IA, 2007