Chemical Distribution - Fire and Explosion

Herrig Brothers Farm Propane Tank Explosion

Albert City, IA · April 9, 1998

What happened

On April 9, 1998, an 18,000-gallon propane tank exploded at the Herrig Brothers farm in Albert City, Iowa. The explosion killed two volunteer firefighters and injured seven other emergency response personnel. Several buildings were also damaged by the blast.

Summary by the US Chemical Safety Board.

Safety recommendations

The CSB made 9 recommendations; none is still open.

To Fire Service Institute of Iowa State University

  • 1998-007-I-IA-7Closed - Acceptable Action

    Ensure that fire fighter training materials address proper response procedures for BLEVEs.

To Herring Brothers Farm

  • 1998-007-I-IA-1Closed - Acceptable Action

    Install protection (i.e., fencing or barricades) to protect aboveground propane pipes from possible damage from vehicles.

  • 1998-007-I-IA-2Closed - Acceptable Action

    Install properly sized propane outlet piping from excess flow valves.

To Iowa State Fire Marshal

  • 1998-007-I-IA-3Closed - Acceptable Action

    Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum the following element: Designation by regulation of the party (such as a facility owner or installer) who is responsible for submitting planned construction or modification documents to the State Fire Marshall.

  • 1998-007-I-IA-4Closed - Acceptable Action

    Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: · Procedures for approving the plans for new or modified installations

  • 1998-007-I-IA-5Closed - Acceptable Action

    Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: Procedures governing the issuance and posting of permits authorizing the use of equipment

  • 1998-007-I-IA-6Closed - Unacceptable Action/No Response Received

    Develop a program to ensure implementation of the requirements of the National Fire Protection Association's NFPA-58 Standard for the Storage and Handling of Liquefied Petroleum Gases, as adopted by Iowa law. Ensure that this program includes, at a minimum, the following elements: · On-site inspections of new, modified, and existing propane and other Liquefied Petroleum Gas storage facilities that are covered by Iowa state law.

To National Propane Gas Association (NPGA)

  • 1998-007-I-IA-8Closed - Acceptable Action

    Ensure that fire fighter-training materials address proper response procedures for BLEVEs.

  • 1998-007-I-IA-9Closed - Acceptable Action

    Distribute the CSB findings and recommendations in this report to NPGA members.